矿井机电硐室火灾的FDS模拟与分析

    FDS Simulation and Analysis of Mine Electromechanical Chamber Fire

    • 摘要: 为了给井下人员在发生机电硐室火灾时的逃生提供参考和依据,采用火灾动态模拟软件PyroSim模拟了吕梁桃园鑫隆煤矿机电硐室火灾的发生,对巷道内气体的温度、毒性,烟雾浓度、可见度进行了分析研究。结果表明,该矿机电硐室火灾发生后火源处温度不断上升,在250 s后趋于稳定,到达约550 ℃;230 s时烟层高度下降至1.6 m,影响工作人员的视线;300 s后巷道内能见度降至1 m,井下人员的逃生难度加大;400 s后巷道内烟气温度达到80 ℃,严重影响人员逃生;巷道内CO浓度始终没有超过临界值,暂且认为对人没有影响。

       

      Abstract: In order to provide reference and basis for the escape of underground personnel in the event of electromechanical chamber fire, the fire dynamics simulation software PyroSim was used to simulate the electromechanical chamber fire occur in Xinlong Coal Mine. The gas temperature, toxicity, smoke concentration, visibility in the roadway are anlyzed. Simulation results showed that the temperature at the fire source kept rising after the electromechanical chamber fire, tended to stabilize after 250 s, reached about 550 ℃; the high-temperature smoke layer dropped to 1.6 m in 230 seconds which greatly influenced the sight of staffs. After 300 s, the visibility in the tunnel decreased to 1 meter, the escape of underground personnel became more difficult. After 400 s, the temperature of flue gas in the roadway reached to 80 ℃, which seriously affected the escape of people. The concentration of CO in the roadway did not exceed critical value, and it had no effect on people.

       

    /

    返回文章
    返回