本安电源双重化保护电路冗余方式对比研究

    Redundancy Modes Comparison Study on Dual Protection Circuit of Intrinsically Safe Power

    • 摘要: 为研究不同的冗余方式对本安电源双重化保护电路的影响,在一种新型截流保护电路的基础上,分别对其进行双重化串联和并联连接,在模拟一个故障前提下,进行对比试验。试验发现当保护电路结构相同时,由于故障类型的不同,双重化串联、并联冗余保护电路会产生不同的保护效果:发生类型I故障,会使串联冗余式保护电路发生误断,导致电源停止供电;发生类型II故障,会使并联冗余式保护电路不能截流,导致安全隐患。不同类型故障是随机发生的,因此当发生一个故障时,2种冗余方式比较,双重化保护电路采用串联冗余式比并联冗余式的安全可靠性更高,更适合工作在爆炸性气体环境中的本安电源使用。

       

      Abstract: In order to study the influence of different redundant ways on dual protection circuit of intrinsically safe power, based on a new type of intercepting protection circuit, the contrast experiment was carried out for dual series and parallel connection respectively under the premise of simulating same fault. The results showed that when the protection circuit had the same structure, the dual series and parallel redundant protection circuit produced different protection effect due to the different fault types. Concretely, the fault I made series redundant protection circuit mistakenly closed, causing power supply stop; the fault II made parallel redundant protection cannot be normally closed, leading to security risks. Since different types of faults occurred randomly, when a single fault occurred, the series redundant dual protection circuit was more secure and reliable than the parallel redundancy ones, it was more suitable for intrinsically safe power working in explosive gas environment.

       

    /

    返回文章